A common fault of diesel generator since starting system
 
发布时间:2015.10.13  浏览次数:
 

    Automation unit since the launch of the fault system is a problem often encountered in the process of maintenance, is also a common faults of automated unit, fault phenomenon to roughly the following: 1, the unit started a cause; 2, power is not start; 3, call non-stop; 4, ATS switch.

    If the problem with one of the generator in use process, please click the following steps to check and troubleshoot:

(1) since the launch of the working system of a power failure. Low power supply voltage or no voltage will cause chaos control logic, causing all kinds of fault. If the power supply is not work properly please check whether the power supply of insurance in good condition, whether line break (happens at wiring is not standard, go trough without metal sheath or wire diameter smaller) whether there is a battery.

(2) start the short circuit or open circuit. A continuity will cause a short circuit will launch a cause, not from the start

(3) the mains and generator blown fuse. Grid safety fuse will cause cause the machine, power electrical blown fuse will lead to ATS can't cut to the generator side.

(4) the ATS switch coil blown fuse, switch to tangential side accordingly.

(5) the starter relay failure, develops in the working environment moisture, relay, poor quality of the generator.

(6) stop relay failure, will cause the generator can't since the downtime.

(7) relay switch failure, will lead to can't switch.

(8) ATS switch failure.

(9) for generator applied voltage comparator, mains side comparator fault causes can't start or start a cause, the generator side comparator fault will cause the ATS switch is not tangential oil machine side.

(10) control the disk failure. Short circuit start line unit does not start or disconnect start line non-stop is generator unit control of the disk failure.

    Since now use since the launch of the system design is various, the brand is very miscellaneous, and vary widely in control circuit, the above analysis can't cover all the fault, just makes a simple analysis of various common faults of the control system, puts forward some emergency treatment, if after the above processing are still unable to troubleshooting. Please contact the supplier or professional maintenance company, to deal with in order to avoid to cause serious consequences.

 

     

PRODUCT

Industrial control systems
Diesel generating se… Diesel generator set… Generator set access… Generating set
Shangchai diesel gen… Weichai diesel gener… Cummins diesel gener… Solar system
Solar energy lamps and lant…
Wall lamp Courtyard Camping
 

ABOUT US

About us
Culture
 

NEWS

Company news
Data download
Technology
 

LINK

Success stories
 
 
Address : 40# Renming Road, Luoshen Twon, Huishan Area, Wuxi City
Copyright(C)2010-2017 Wuxi Shuo Zhuo electrical technology co.,ltd.   Legal notices Contact us